visitor@assetos.io:~$ assetos compliance --check fire-ext
62 units · monthly visual done
4 units annual service due
CO2 pair · extended service 2027
visitor@assetos.io:~$

Fire Extinguisher Service Frequency (UK): BS 5306-3 Explained

Fire extinguisher servicing is one of those compliance regimes that looks simple — "get them serviced once a year" — and then turns out to have four distinct schedules running at once, per extinguisher, with different rules by type. Miss one and the consequences stack: voided insurance, a failed fire risk assessment, and enforcement under the fire safety order.

Here's the full schedule under BS 5306-3, who's allowed to do what, and a free log to track it.

The Regulatory Reform (Fire Safety) Order 2005 (England and Wales; Scotland and Northern Ireland have equivalents) requires the responsible person to keep firefighting equipment maintained in efficient working order and good repair. The Order doesn't specify intervals — BS 5306-3 is the recognised standard that defines what "maintained" means in practice, and it's what fire risk assessors, insurers, and courts benchmark against.

The Four Schedules

1. Monthly visual check — by you. The responsible person (or someone delegated) checks each extinguisher: in its designated place, unobstructed, visible; pressure gauge in the green; safety pin and tamper seal intact; no visible damage or corrosion. No engineer needed — but it should be recorded.

2. Annual basic service — by a competent person. A trained service technician (BAFE-registered companies are the recognised route) examines each extinguisher: weight checks, pressure verification, hose and horn condition, corrosion, and re-tagging. This is the "annual service" everyone knows — necessary, but not sufficient on its own.

3. Extended service — every 5 years (water, foam, powder). The extinguisher is discharged, internally examined, and refilled. This is the one that gets missed, because it only comes around twice a decade and the sticker from the last basic service looks reassuring.

4. CO2 extinguishers — 10-year overhaul. CO2 units skip the 5-year discharge but require overhaul including hydrostatic pressure testing of the cylinder at 10 years, done at a specialist facility (usually a service exchange).

Plus a commissioning service when each extinguisher is first installed — new units aren't compliant just because they arrived in a box.

CheckFrequencyWho
Visual checkMonthlyResponsible person (in-house)
Basic serviceAnnualCompetent person (e.g. BAFE)
Extended service (water / foam / powder)Every 5 yearsCompetent person
Overhaul incl. hydrostatic test (CO2)Every 10 yearsSpecialist facility
CommissioningOn installationCompetent person

Why This Regime Slips

Each extinguisher carries its own clock: the site with 60 extinguishers installed over fifteen years has 60 annual dates, 40-odd extended-service dates, and a handful of CO2 overhauls — none of them aligned. The monthly visual is a discipline problem; the 5- and 10-year events are a memory problem. Spreadsheets handle the first badly and the second worse, because a date five years out is exactly the kind that survives three staff changes and then expires silently — the compliance-spreadsheet failure mode in its purest form.

Tracking It

Minimum viable records: a register of extinguishers (ID, type, location, install date) with the next-due date for each schedule, plus a log of monthly visuals and services with certificates attached.

Free template — monthly visual log, annual service record, and 5-year certificate log in one workbook (also available on the fire extinguisher tool page):

Fire Extinguisher Service Log

Enter your email to download the free BS 5306-3 service log pack. We'll also send a copy via email.

Free download. No spam. Unsubscribe anytime.

Fire extinguishers are also rarely the only fire-safety clocks running — alarm tests are weekly, emergency lighting monthly and annually, fire doors annually. If your compliance calendar is spreading across regimes (PAT, legionella, LOLER), the fix is structural: every extinguisher an asset with its own service schedules, reminders that fire ahead of each due date, and certificates stored against the unit. That's the shape of thing a compliance-first CMMS does by default.

Sixty extinguishers, zero missed dates